IVECO (30-796kVA)

OPEN GENSETS WITH AIRCOOLED DEUTZ ENGINE

1500 RPM 400/230 V 50 Hz Type AD-020 20/16 Kva/KW (PRP) 21/16,8 Kva/KW (LTP)

Engine: F3L2011

Alternator: ECO28-1L/4

Scope of Supply:

The engine and the alternator are mounted together forming a rigid monoblock, the shafts are connected by a flexible

disc connection. The monoblock is mounted on a steel base frame via silent blocks. The base frame is including a fuel

tank. Starting is electric and it includes a battery. The genset monitoring system consist of a control module.

GEN SET POWER

Voltage Hz Phase Cos Ø PRP* Kva/KW LTP** Kva/KW Amp.

415/240 50 3 0,8 20/16 21/16,8 29,2

400/230 50 3 0,8 20/16 21/16,8 30,3

380/220 50 3 0,8 20/16 21/16,8 31,9

240/120 50 3 0,8 20/16 21/16,8 50,6

230/115 50 3 0,8 20/16 21/16,8 52,8

220/110 50 3 0,8 20/16 21/16,8 55,2

PRP* Kva/KW:

Available electrical power (at a variable load) with a medium of 80% of the indicated maximum power. A 10% overload capability is available

LTP** Kva/KW:

Available electrical load (at a variable load) during a maximum of 500 hours per year. No overload capability is available.

Control Cubicle Alternatives

Manual/Remote Control Cubicle:: STANDARD MCP SAM 712

Automatic Control Cubicle: PLEASE CONSULT

Options::

Please see the price list

 

TECHNICAL DATA

Engine Alternator

Engine type: F3L2011 Alternator Type: ECO28-1L/4

Eng. Power kW COP: 18,1 Nº of poles: 4

Eng. Power kW PRP: 19 Eff. At 3/4 %: 88

Eng. Power kW LTP: 20 Eff. At 4/4 %: 87,6

Nº Cylinders: 3 Alt. rating PRP kVA III Kw II: 20

Displacement cm3: 2330 Alt. rating LTP kVA III kW II: 22

Bore/stroke (mm/mm): 947112 Output Power PRP kVA III kW II: 20

Compression ratio: 19 Output Power LTP kVA III kW II: 21,9

Cooling: AIR Current Amp PRP: 29,5

Injection: DIRECT Current Amp LTP: 31,4

Aspiration: NATURAL Standard Circuit Breaker (Amp): 32 IV

Standard governor: MECHANICAL Xd (%): 175

Governing control quality: G2 X'd (%): 16,5

Speed droop mech gov. (%): 5 X: 9,4

Exhaust gases temperature (ºC): 510 Nº of wires: 12

Exhaust gases flow (m3/h): 230 Insulation: H

Max Exh. Back pres. (mbar): 30 Regulator AVR: SR7/2

Coolant capcity (lit.): - Protection: IP23

Cooling air flow (m3/h): ? DIMENSIONS

Max allow. Intake dep. (mbar): 20 Height: 1100 mm

Combustion air flow (m3/h): 86 Width: 620 mm

Oil cap. (Litres): 5,5 Lenght: 1440 mm

Oil cons. (kg/hr or % of fuel cons): 0,30%

Min oil press warning (bar): 2,1 Weight: 540 kgs

Fuel cons. 25% lit/h: 2,3

Fuel cons. 50% lit/h: 2,9 Tank: 36 lit

Fuel cons. 75% lit/h: 3,9

Fuel cons. 100% lit/h: 5

Electric system VDC: 12

Type: Neg to ground.

Battery (Ah): 60

Starting motor (kW): 3

Flywheel Housing: SAE3/11,5

Technical information available in download section.:

Engine technical data Alternator Technical data Gen Set Drawing Instalation drawing Control cubicle descr.

Engine manual Alternator Manual Gen Set Manual Gen Set Condensed Man. Controler manual

 

Control Cubicles

MANUAL -REMOTE START CONTROL MODULE: MCP SAM 712

SAM 712 CONTROLLER

•Manual or Automatic remote start controller, Selector switch for Off, Man and

Auto with key. Complete engine protection functions with alarms visualised via

LEDs in the front. The controller is set up via 6 DIP switches in the rear of the

case.

•Standard circuit breaker.and diferential relay.